Date of Analysis :February 13, 2018 / May 2, 2018
A. PHYSICAL TEST RESULT
PUMPING STATION | PHYSICAL TEST | METAL ANALYSIS | ||||
TURBIDITY | Color | Arsenic | Cadmium | Lead | REMARKS | |
PNSDW LIMITS | 5 NTU | 10 ACU | 0.01 mg/L | 0.003 mg/L | 0.01 mg/L | |
1. Pump # 1 - Existing | 1 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
2. Pump # 3 | 1 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
3. ENRICA | 1 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
4. Pump # 4 | <0.005 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
5. SAWMILL | 1 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
B. CHEMICAL TEST RESULT
PUMPING STATION | Fecal Coliforms | E.Coli | pH |
Chlorine, Residual |
Total Dissolved Solids | Nitrate | REMARKS |
PNSDW LIMITS | <1.1 | Negative | 6.5 - 8.5 | 0.3-1.5 | 500 | 50 | |
1. Pump # 1 - Existing | <1.1 | Negative | 8.5 | 1.0 | 214 | 0.2 | PASSED |
2. Pump # 3 | <1.1 | Negative | 7.1 | 0.5 | 270 | 12 | PASSED |
3. ENRICA | <1.1 | Negative | 8.2 | 0.8 | 249 | 0.06 | PASSED |
4. Pump # 4 | <1.1 | Negative | 8.4 | 0.7 | 197 | 0.06 |
PASSED |
5. SAWMILL | <1.1 | Negative | 8.5 | 1.0 | 132 | 0.2 | PASSED |
Note
PNSDW : Philippines National Standards for Drinking Water
NTU : Nephelometric Turbidity Unit/ A unit measuring the lack of clarity of water
ACU : Apparent Colour Unit