MENU

 

Date of  Analysis : May 5, 2017

A. PHYSICAL TEST RESULT

PUMPING STATION PHYSICAL TEST METAL ANALYSIS
TURBIDITY Color Iron Mangenes Arsenic Cadmium Lead REMARKS
PNSDW LIMITS 5 NTU 10 ACU 1 mg/L 0.40 mg/L 0.05 mg/L 0.003 mg/L 0.01 mg/L
1. Pump # 1 - Existing 1.6 3 0.1 <0.01 <0.01 <0.003 <0.003 PASSED
2. Pump # 3  0.4 <3 <0.05 <0.01 <0.01 <0.003 <0.003 PASSED
3. ENRICA 0.9 <3 <0.05 <0.01 <0.01 <0.003 <0.003 PASSED
4. Pump # 4 0.35 <3 0.1 <0.01 <0.01 <0.003 <0.003 PASSED
5. SAWMILL 3.7 3 <0.05 <0.01 <0.01 <0.003 <0.003 PASSED

 

B. CHEMICAL TEST RESULT

PUMPING STATION pH Chloride Total Dissolved Solids Nitrate Sulfate Benzene REMARKS
1. Pump # 1 - Existing 6.5 - 8.5 250 500 50 250 Absence PASSED
2. Pump # 3  6.5 - 8.5 250 500 50 250 Absence PASSED
3. ENRICA 6.5 - 8.5 250 500 50 250 Absence PASSED
4. Pump # 4 6.5 - 8.5 250 500 50 250 Absence PASSED
5. SAWMILL 6.5 - 8.5 250 500 50 250 Absence PASSED

Note
PNSDW : Philippines National Standards for Drinking Water
NTU : Nephelometric Turbidity Unit/ A unit measuring the lack of clarity of water
ACU : Apparent Colour Unit

WATER QUALITY TEST 2021

WATER QUALITY TEST 2020

WATER QUALITY TEST 2019

WATER QUALITY TEST 2018