Date of Analysis : February 17, 2021 / March 31, 2021

A. PHYSICAL TEST RESULT

PUMPING STATION PHYSICAL TEST METAL ANALYSIS
TURBIDITY Color Arsenic Cadmium Lead REMARKS
PNSDW LIMITS 5 NTU 10 ACU 0.01 mg/L 0.003 mg/L 0.01 mg/L
1. Pump # 1 - Existing 0.4 3 <0.008> <0.001 <0.005 PASSED
2. Pump # 3  1.4 3 <0.008> <0.001 <0.005 PASSED
3. ENRICA 0.35 3 <0.008> <0.001 <0.005 PASSED
4. Pump # 4 0.4 3 <0.008> <0.001 <0.005 PASSED
5. SAWMILL 1.55 5 <0.004> <0.001 <0.001 PASSED
6. MAGSAYSAY 1 0.35 3 <0.008> <0.001 <0.005 PASSED
7.MAGSAYSAY 2 0.2 3 <0.008> <0.001 <0.005 PASSED


 

B. CHEMICAL TEST RESULT

PUMPING STATION Fecal Coliforms E.Coli pH

Chlorine, Residual

Total Dissolved Solids Nitrate REMARKS
PNSDW LIMITS <1.1 Negative 6.5 - 8.5 0.3-1.5 500 50
1. Pump # 1 - Existing <1.1 Negative 8.3 0.6 206 <0.006 PASSED
2. Pump # 3  <1.1 Negative 7.0 1.5 392 9.8 PASSED
3. ENRICA <1.1 Negative 8.3 1.3 209 0.03 PASSED
4. Pump # 4 <1.1 Negative 6.9 1.1 370 0.2 PASSED
5. SAWMILL <1.1 Negative 8.29 0.3 156 20.39 PASSED
6. MAGSAYSAY 1 <1.1 Negative 8.3 0.9 204 <0.006 PASSED
7. MAGSAYSAY 2 <1.1 Negative 8.3 0.3 212 <0.006 PASSED

 

Note
PNSDW : Philippines National Standards for Drinking Water
NTU : Nephelometric Turbidity Unit/ A unit measuring the lack of clarity of water
ACU : Apparent Colour Unit

 