Date of Analysis : February 17, 2021 / March 31, 2021
A. PHYSICAL TEST RESULT
PUMPING STATION | PHYSICAL TEST | METAL ANALYSIS | ||||
TURBIDITY | Color | Arsenic | Cadmium | Lead | REMARKS | |
PNSDW LIMITS | 5 NTU | 10 ACU | 0.01 mg/L | 0.003 mg/L | 0.01 mg/L | |
1. Pump # 1 - Existing | 0.4 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
2. Pump # 3 | 1.4 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
3. ENRICA | 0.35 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
4. Pump # 4 | 0.4 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
5. SAWMILL | 1.55 | 5 | <0.004> | <0.001 | <0.001 | PASSED |
6. MAGSAYSAY 1 | 0.35 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
7.MAGSAYSAY 2 | 0.2 | 3 | <0.008> | <0.001 | <0.005 | PASSED |
B. CHEMICAL TEST RESULT
PUMPING STATION | Fecal Coliforms | E.Coli | pH |
Chlorine, Residual |
Total Dissolved Solids | Nitrate | REMARKS |
PNSDW LIMITS | <1.1 | Negative | 6.5 - 8.5 | 0.3-1.5 | 500 | 50 | |
1. Pump # 1 - Existing | <1.1 | Negative | 8.3 | 0.6 | 206 | <0.006 | PASSED |
2. Pump # 3 | <1.1 | Negative | 7.0 | 1.5 | 392 | 9.8 | PASSED |
3. ENRICA | <1.1 | Negative | 8.3 | 1.3 | 209 | 0.03 | PASSED |
4. Pump # 4 | <1.1 | Negative | 6.9 | 1.1 | 370 | 0.2 | PASSED |
5. SAWMILL | <1.1 | Negative | 8.29 | 0.3 | 156 | 20.39 | PASSED |
6. MAGSAYSAY 1 | <1.1 | Negative | 8.3 | 0.9 | 204 | <0.006 | PASSED |
7. MAGSAYSAY 2 | <1.1 | Negative | 8.3 | 0.3 | 212 | <0.006 | PASSED |
Note
PNSDW : Philippines National Standards for Drinking Water
NTU : Nephelometric Turbidity Unit/ A unit measuring the lack of clarity of water
ACU : Apparent Colour Unit